Current transducer MB-1I-1 5A
MB-1I-1 transducer is designed to measure the strength of alternating current and direct current and to transmit the data via RS-485 port using MODBUS RTU protocol.
Functioning
The module is designed to work with current transformer with 5 A secondary current.
The module continuously measures the current flowing through the measurement input. Readout of recorded current strength, setting of all communication parameters are all carried out through RS-485 port using the MODBUS RTU communication protocol. Power up is indicated by a green LED U light. Valid data exchange between the module and the second device is indicated by a yellow LED Tx light.
The transducer measures the effective value of TrueRMS current, which ensures high accuracy even with distorted flow.
Reset communication settings
Under cover is available code switch.
Details of resetting available in the instructions below.
- Power supply voltage
- 9÷30 V DC
- WE-WY breakthrough voltage
- 2,1 kV
- ports
- RS-485
- Communication protocol
- MODBUS RTU
- The type of work
- SLAVE
- Baudrate
- 1200÷115200 bit/s
- Data bits
- 8
- Stop bits
- 02-sty
- Bits of parity
- EVEN / ODD / NONE
- Address
- 1÷247
- Maximum measuring error
- 0,50%
- Measurement range TrueRMS / maximum voltage
- 0÷5 A AC/85 V AC
- Power consumption (max)
- 50 mA
- Precision of reading the register
- 0,1 A
- Sampling frequency
- 10 Hz
- Relative air humidity (for 30
- 85%
- Terminal
- pluggable terminal blocks 2,5 mm²
- Tightening torque
- 0,4 Nm
- Dimensions
- 1 module (18 mm)
- Assembly
- on rail 35 mm
- Ingress Protection Marking
- IP20
Protocol parameters MODBUS RTU