Temperature transmitter MB-TC-1
Temperature transducer.
The device measures temperature with the use of various types of thermocouples. Works with thermocouples of the following types: K, J, E, N, T, S, R, B.
The transmitter measures the current temperature of the hot junction (thermocouples) and the cold junction (temperature at the point of connection of the thermocouple). Thanks to this measurement, it is possible to provide the relative and absolute temperature of the object on which the measurement is made. The device has the ability to set 4 independent alarms. Each of the alarms has the option of setting the hysteresis of operation on the level of 0 ÷ 256 ° C and 2 triggering modes:
- the alarm reacts to lowering the temperature below the set value;
- the alarm reacts to an increase in temperature above the set value.
- Power supply voltage
- 9÷30 V DC
- Measurement range
- Depends on the type of sensor
- ports
- RS-485
- Temperature probe
- K, J, E, N, T, S, R, B
- Communication protocol
- MODBUS RTU
- The type of work
- SLAVE
- Baudrate
- 1200÷115200 bit/s
- Data bits
- 8
- Stop bits
- 1 / 1.5 / 2
- Bits of parity
- EVEN / ODD / NONE
- Address
- 1÷247
- Maximum measuring error
- ±2°C
- Sampling frequency
- 10 Hz
- Terminal
- pluggable terminal blocks 2,5 mm²
- Tightening torque
- 0,4 Nm
- Power consumption
- 0,3 W
- Working temperature
- -20÷50°C
- Dimensions
- 1 module (18 mm)
- Assembly
- on rail 35 mm
- Ingress Protection Marking
- IP20