Current transformer TI-600
search
  • Current transformer TI-600
  • Current transformer TI-600
  • Current transformer TI-600
  • Current transformer TI-600

TI-1000 current transformer

TI-1000-5, 5902431675404

Single-phase,
withclosed core.
Gear 1000/5.
Power 10 VA.

Current transformer is used to proportionally change large current intensities to lower values, adapted to the measuring ranges of control and measurement devices.

Operation
The wire with the measured current passes through the main opening of the current transformer (P1/P2), which is equivalent to one winding of the primary winding. The terminals of the secondary winding S1 and S2 are connected to the terminals of the measuring circuit of the control or measuring device.
The ratio of the intensities of the currents in the two windings is a constant quantity and is called the current ratio: IPn/ISn=N, where IPn - rated primary current; ISn - rated secondary current; N - value of transmission ratio. From the value of the current flowing through the secondary winding, the value of the current flowing through the primary winding can be determined: ISm*N=IPm, where ISm - measured primary current; IPm - measured secondary current.

Note!
Recommended to connect the secondary system with a wire with a diameter of not less than 2.5 mm².
Recommended grounding of the S2 terminal.
Prohibit disconnection of the secondary circuit during operation of the current transformer (possibility of high voltage resulting in paralysis of persons or damage to the device).

TI-1000-5
Type
single-phase
Building
with close core
Transmission lp / ls
1000/5
Class
0,5
Power [VA]
10 VA
Frequency
50÷60 Hz
Maximum working voltage
0,66 kV AC
Standard number
IEC 60044-1
Nominal secondary current Is
5 A
Isolation breakdown voltage
3 kV/1 min.
Security factor
FS ˂ 5
Connection S1 / S2
zaciski śrubowe 4 mm²
Tightening torque
0,5 Nm
Working temperature
-5÷40°C
Mounting position
vertical/horizontal
Assembly
blackboard / busway
Ingress Protection Marking
IP20







type Ip/Is class power  
[VA]
hole dimensions P1/P2
A1/A2/A3×B; C [mm]
dimensions
W×H [mm]
weight
[kg]
TI-30*  30/5  1 2,5 Ø22 44×67×30 0,135
TI-40 40/5 1 1 Ø22  44×67×30 0,135
TI-50 50/5 1 1,5 Ø22  44×67×30 0,135
TI-60 60/5 1 1,5 Ø22  44×67×30 0,135
TI-75 75/5  1 1,5 Ø22 44×67×30 0,135
TI-80 80/5 1 1,5 Ø22  44×67×30 0,135
TI-100  100/5  0,5
2,5 30/25/20×10; Ø22 61×81×34  0,235
TI-150 150/5 0,5 2,5 30/25/20×10; Ø22  61×81×34  0,235
TI-200 200/5 0,5 5,0 30/25/20×10; Ø22  61×81×34  0,235
TI-250 250/5 0,5 5,0 30/25/20×10; Ø22  61×81×34  0,235
TI-300 300/5  0,5 5,0 30/25/20×10; Ø22 61×81×34  0,235
TI-400 400/5  0,5 10 40/30/ - ×10; Ø30  75×99×40  0,305
TI-600 600/5 0,5 10 40/30/ - ×10; Ø30  75×99×40  0,305
TI-1000 1000/5  0,5 10 62/52/38×21; Ø46 126×102×62 -
TI-1250 1250/5 0,5 10 62/52/38×21; Ø46  126×102×62 -
TI-1600 1600/5  0,5 10 62/52/38×21; Ø46 126×102×62 -



Attention! 
Applies only to TI-30

* For correct operation of the transformer, a 4-fold transmission of the current cable through the transformer's opening is required.