Timing relays PCR-513
search
  • Timing relays PCR-513
  • Timing relays PCR-513
  • Timing relays PCR-513

Timing relays PCR-513-16

PCR-513-16, 5902431672083
Timing relays are devised to time the control of industrial and domestic automatic control engineering systems (e.g. ventilation, heating, lighting, signalling, etc.).
Operation mode: Lagged activation.

Functioning
After the power voltage is supplied, the contact remains in position 11-10 and the timing of the preset value t is commenced. After the preset time t has been counted down, the contact is shifted to position 11-12. The working sequence of the relay may be repeated after turning the power supply off and on.

 


 

Attention!
* Setting the time range knob regulator in the:
  ON - position with power supply activated results in the permanent closure of the contact in position 11-12.
  OFF - position (power supply activated) causes the contact to be permanently closed in the 11-10 position.
* With the power supply on, the system does not respond to time range setting modifications.
* The newly set time range is active after the power supply has been turned off and on.
* With the power supply on, it is possible to regulate the preset time freely within the selected time range.

 

PCR-513-16
Power supply voltage
230 V AC
Operating mode
lagged activation
The executive element
relay
Maximum load current
16 A
Contact configuration
1 × NO/NC
Separation of the contact
YES
Contact status indication
LED red
Operating time - adjustable
0,1 s ÷ 576 godz.
Power indication
LED green
Terminal
pluggable terminal blocks 2,5 mm²
Tightening torque
0,4 Nm
Power consumption
0,8 W
Working temperature
-25 ÷ 50 °C
Dimensions
1 module (18 mm)
Assembly
on rail 35 mm
Ingress Protection Marking
IP20